PID Testing  
 
       
  Live line detection of unctured insulators.  
   
     
  Punctured Insulator Detection.  
  A) By Electric field Measurement Method  
 
This equipment named as POSITRON is used for detecting leakage in the defective insulator in the string.
This equipment is attached to hot stick & it is moved across each insuator in the insulator string & it records the electrical field surrounding the insulators.
The electrical field surrounding an insulator decreases considerably in front of a
defective insulator.
The downloaded data gives us graphical presentation of the field against each insulator of the complete string, enabling us to identify the defective insulator.
The software data analysis eliminates the need for operator interpretation.
 
     
  B) By Voltage Measurement Method  
 
In this method the voltage difference across each disc is made use for measuring the leakage current in m A by connecting galvanometer in shunt
If an insulator becomes weak or gets punctured thevoltage difference across that disc becomes zero and the care of that voltage is taken by adjacent discs.
The punctured insulator is identified by sudden deep in the galvanometer and indicates its replacement
 
     
  Punctured Insulator Detector  
 
Positron Make Electric Field
Measurement Type Instrument
Ritz Make Voltage Measurement
Type Instrument
 
     
  Graph Showing Condition Of The Insulator String By Positron Method.  
 
Disc Insulator No.4 In
The String Is Defective.
Graph Of Healthy
Insulator String.
 
     
  Advantages of PID testing.  
 
No outage, so no interruption to consumers
No revenue loss
Problem is highlighted immediately, hence further breakdown may be avoided.
Emergency outage is avoided
Contaminated disc insulators can be cleaned by hot line washing, so flashover of disc insulators resulting in to break-down can be avoided.
 
     